Quick Answer

The best ultrasonic flow meter for water is usually a transit-time clamp-on meter: it straps onto the outside of an existing PVC, PE, steel or cast-iron pipe, needs no shutdown or cutting, and has no wetted parts. Choose it by pipe size and material, accuracy class, output signal (4-20 mA, RS485 Modbus, pulse) and whether the installation is permanent or portable.

How an Ultrasonic Flow Meter Measures Water

A clamp-on ultrasonic flow meter uses two transducers fixed to the outside of the pipe with stainless-steel straps and couplant. One pulse travels with the flow and one against it. Water moving through the pipe makes the downstream pulse arrive slightly earlier than the upstream pulse; the transmitter converts that time difference into velocity and, using the pipe inner diameter you enter, into volume flow in m³/h or the unit you configure. This transit-time principle is the one described for liquids in closed conduits in ISO 12242 — Measurement of fluid flow in closed conduits: ultrasonic transit-time meters for liquid. For the formula and a worked nanosecond example, see how a clamp-on ultrasonic flow meter works.

Because nothing is inserted into the pipe, there is no pressure drop, no risk of leaks at a new flange and no contact with potable water. That is why clamp-on meters are widely used for retrofit metering of water mains, pump stations and building services where the line cannot be taken out of service.

Diagram of a clamp-on ultrasonic flow meter on a full water pipe in V-mode: two transducers, reflected pulse path, 10D upstream and 5D downstream straight run, transmitter with 4-20 mA, RS485 and pulse outputs
V-mode transit-time measurement on a water pipe: both transducers on one side, the pulse reflects off the opposite wall, and the transmitter outputs 4-20 mA, RS485 Modbus RTU and pulse.

Water Applications and What Each One Needs

Water flow measurement covers very different duties. The table below matches typical water applications to the meter configuration and the points to confirm before ordering.

ApplicationTypical pipeSuggested SEGMENsensor configurationConfirm before ordering
Water supply mains and district meteringDuctile/cast iron, steel, PE; large diametersFixed U10 / U10S PRO, or U11 for ±0.5% or pipes above 1200 mm; Z-mode on large pipesPipe OD and wall thickness, liner, straight run, RS485 to SCADA
Pump station and borehole dischargeSteel or PEFixed U10 with 4-20 mA to the pump PLCDistance from pump outlet and valves, full pipe at all times
Boiler feed and industrial make-up waterCarbon steel, stainless steelFixed U10 series, 4-20 mA or pulse output for volume totalizingLiquid temperature against the transducer rating, full pipe, straight run upstream
HVAC chilled and condenser waterSteel, copperU10 series or U11 in the energy (BTU) version with PT1000 sensors; RS485 Modbus to the BMSLiquid temperature, insulation removal at the measuring section
Treated effluent and process cooling waterSteel, stainless steel, PVCFixed U10 / U10S PRO or U11Solids and air content; transit-time needs a clean single-phase liquid
Water audits, leak surveys and commissioningAny of the aboveU20 portable meter with data loggerPipe size range of the transducer pair supplied

Five Selection Steps for a Water Flow Meter

  1. Measure the real pipe, not the nominal size

    Record outer diameter, wall thickness, pipe material and any internal liner. An incorrect outer diameter becomes a systematic error in every reading, so measure it with a circumference tape or calipers.

  2. Find a full, straight section

    Transit-time meters need a pipe that is always full at the measuring point and a straight run of at least 10D upstream and 5D downstream of elbows, valves and pumps. On horizontal pipes, mount the transducers at the side (3 or 9 o'clock) to avoid air at the top and sediment at the bottom.

  3. Choose the accuracy class

    For process control and water balance, the U10 series and U20 are specified at ±1%, and the U11 at ±0.5% with 0.1% repeatability. U12 (±2%) and U13 (<3% FS) suit indication and trend monitoring. Compare every model in our U10 to U20 clamp-on flow meter model comparison.

  4. Match the output to your control system

    Use 4-20 mA for a PLC analog input (signal levels per IEC 60381-1 analogue direct current signals), RS485 Modbus RTU for SCADA or a BMS, pulse output for totalizing and relay for low-flow alarms.

  5. Decide between fixed and portable

    Permanent metering uses a wall-mount transmitter powered from 10–36 V DC, with 90–245 V AC as an option on the U10 series and as a standard choice on the U11. Surveys, leak checks and verification of existing meters use the battery-powered U20 portable clamp-on flow meter.

If your design flow is in US gpm and the meter datasheet in L/min or m³/h, convert it first with the GPM to m³/h and L/min converter (1 US gpm = 0.227125 m³/h).

Send us your pipe data for a water flow meter quotation

Tell us the pipe OD, wall thickness and material, liner, water temperature, available straight run, output signal and quantity. OEM volume supply · samples 1–5 pcs in 5–7 days · production lead time confirmed with the quotation · quotation within 24 hours.

What straight pipe run does a clamp-on flow meter need?

A clamp-on ultrasonic water flow meter needs at least 10 pipe diameters (10D) of straight, full pipe upstream of the transducers and 5D downstream, measured from the nearest elbow, tee, valve or pump. D is the pipe inner diameter, so a DN100 line needs about 1.0 m upstream and 0.5 m downstream. This 10D / 5D figure is the minimum on the SEGMENsensor ultrasonic flow meter product page for a single elbow; pumps, partly open control valves and two elbows in different planes need a longer upstream run, listed in the straight-run table of our installation guide.

Illustration of the straight pipe run for a clamp-on ultrasonic water flow meter: at least 10D upstream after a 90 degree elbow and 5D downstream before a valve, transducers at the side of a horizontal pipe, DN100 worked example
Illustration: 10D upstream and 5D downstream of the clamp-on transducers on a horizontal water pipe, with the transducers at the side of the pipe. Lengths for DN100 are calculated values.

Installing an ultrasonic water flow meter in six steps

  1. Pick a full, straight section

    Choose a point with at least 10D straight pipe upstream and 5D downstream where the pipe is always full. A vertical section with upward flow is preferred; avoid high points where air collects and the first metres after a pump.

  2. Set the mounting position

    On a horizontal pipe, mount the transducers at the side (3 or 9 o'clock) so that air at the top and sediment at the bottom do not block the ultrasonic path.

  3. Enter the pipe data

    Key in the measured outer diameter, wall thickness, pipe material, any liner and the liquid (water). The transmitter then calculates the transducer spacing.

  4. Choose V-, Z- or W-mode

    V-mode is the default for about DN50–DN300, Z-mode for DN300 and above or when the V-mode signal stays weak, and W-mode only on clean, thin-walled DN15–DN50 pipes.

  5. Prepare the surface and clamp the transducers

    Remove paint, rust and scale at the contact points, apply couplant, set the calculated spacing and tighten the stainless-steel straps or rail.

  6. Check signal quality and record a first reading

    Signal quality should be above 60%. If it is lower, re-clean the surface, re-apply couplant, check the spacing or switch to Z-mode, then record the first stable reading.

Quick selection: straight run, model and mounting mode by pipe size

Straight-run lengths below are calculated as 10 × and 5 × the nominal size; use the measured inner diameter of your pipe for the final layout. Model ranges are taken from the specification table below.

Pipe sizeUpstream 10D, m (ft)Downstream 5D, m (ft)Typical mountingSEGMENsensor models covering this size
DN25 (1")0.25 (0.8)0.13 (0.4)W- or V-modeU13, U12, U10S PRO, U10, U11, U20
DN50 (2")0.5 (1.6)0.25 (0.8)V-mode (W-mode on clean, thin-walled pipe)U12, U10S PRO, U10, U11, U20
DN100 (4")1.0 (3.3)0.5 (1.6)V-modeU10S PRO, U10, U11, U20
DN150 (6")1.5 (4.9)0.75 (2.5)V-modeU10S PRO, U10, U11, U20
DN300 (12")3.0 (9.8)1.5 (4.9)V- or Z-modeU10S PRO, U10, U11, U20
DN600 (24")6.0 (19.7)3.0 (9.8)Z-modeU10S PRO, U10, U11, U20
DN1200 (48")12 (39.4)6 (19.7)Z-modeU10S PRO, U10, U11, U20
DN1400–DN500014–50 (46–164)7–25 (23–82)Z-modeU11

Send the pipe size, material, liner and the straight-run lengths you have on site with your inquiry; our application engineers confirm the mounting mode and transducer type for each measuring point.

Watch: clamp-on ultrasonic flow meter installation, step by step

Clamp-on ultrasonic flow meter installation guide video: straight run, pipe data, V/Z/W mounting, couplant and signal strength
Clamp-On Ultrasonic Flow Meter Installation: Complete GuideSite check and straight run (10D upstream / 5D downstream), pipe data, V/Z/W mounting, couplant, transducer spacing, wiring, signal strength and quick fixes.

Request an engineering review of your pipe layout

Send a photo or sketch of the pipe run with the straight lengths marked, plus pipe OD, wall thickness, material and output signal. OEM volume supply · qualification samples 1–5 pcs in 5–7 working days · production lead time and MOQ confirmed with the quotation · reply within 24 hours. Datasheet: clamp-on ultrasonic flow meter datasheet (PDF).

SEGMENsensor Clamp-On Flow Meter Specifications for Water

The values below are taken from the SEGMENsensor ultrasonic flow meter product page and datasheet.

ParameterU10 / U10S PRO (wall-mount)U11 (high accuracy)U12 / U13 (one-piece)U20 portable
Measuring principleTransit-time
Pipe size25–1200 mm (U10) · 15–1200 mm (U10S PRO)15–5000 mmDN15–DN65 (U12) · DN15–DN40 (U13)25–1200 mm (1"–48")
Accuracy±1%±0.5%±2%, ±1% calibrated (U12) · <3% FS, <1.5% FS calibrated (U13)±1%
Repeatability0.2%0.1%——
Velocity range±0.03 to ±5 m/s±0.01 to ±12 m/s0.03–10 m/s (U12) · 0.15–10 m/s (U13)±0.01 to ±12 m/s
Sensor temperature−40 to +80 °C standard; +130 °C (H1A), +180 °C (H2A); DN15–DN40 sensors 0–65 °C or 0–115 °CSame sensors as the U10 series0–65 °C or 0–115 °C (U12) · −10 to +65 °C or +105 °C (U13)−40 to +80 °C (P2) or +130 °C (P2H)
Pipe materialsSteel, stainless steel, copper, cast iron, PVC, PE and most plastics
OutputsChoose two: 4-20 mA, pulse (OCT), relay, RS232 / RS485 Modbus; HART optionalChoose two: 4-20 mA, pulse (OCT), relay, RS232 / RS485 Modbus; HART optionalU12: choose two of 4-20 mA, RS485 Modbus, OCT, relay · U13: 4-20 mA + RS485 Modbus, pulse or relay optionalChoose two: 4-20 mA, RS485 Modbus, OCT, relay; SD card logging up to 32 GB
Power supply10–36 V DC; 90–245 V AC optional90–245 V AC or 10–36 V DC10–24 V DC (U12) · 20–28 V DC (U13)3000 mAh rechargeable lithium battery, about 16 h per charge
Protection ratingTransmitter IP65, sensors IP68Sensors IP68IP65 (U12)Sensors IP68
CertificationCE, UKCA
MOQ / lead timeConfirmed with the quotation

Protection ratings follow the IP code defined in IEC 60529 — Degrees of protection provided by enclosures (IP Code). For pits and chambers that can flood, specify IP68 transducers and route the cable to a transmitter mounted above the flood level.

Download the one-page datasheet (PDF)

Pipe size ranges, accuracy, transducer types and temperature ratings, outputs, power supply, enclosure ratings and ordering code for the SEGMENsensor clamp-on ultrasonic flow meter range. No registration required.

Portable Meters for Water Audits and Leak Surveys

Utilities and facility teams often need to check a flow reading before deciding where a permanent meter belongs. A portable clamp-on meter does this in minutes: strap on the transducers, enter the pipe data, and log flow over a full demand cycle to compare night flow with day flow or to verify an existing inline meter. The U20 stores data on an SD card for reporting. For the pump station side — per-pump flow, DMA inlets and how to judge a meter check — see clamp-on flow meters in water pump stations.

SEGMENsensor U20 portable handheld clamp-on ultrasonic flow meter for water audits and leak surveys
SEGMENsensor U20 portable clamp-on flow meter: battery powered, with data logger and SD card, for water audits, leak surveys and meter verification.

Common Mistakes on Water Pipes

  • Measuring right after a pump or valve. Swirl and turbulence make readings unstable; keep at least 10D upstream and 5D downstream.
  • Partially filled pipes. Gravity lines and high points can run partly full; a transit-time meter needs a full pipe at the measuring point.
  • Ignoring the liner. Cement or thick rubber linings change the acoustic path; enter liner material and thickness or choose a different section.
  • Wrong pipe data. A nominal size from a drawing is not the actual outer diameter; measure it on site.

The full mounting procedure, including V-, Z- and W-mode spacing, is in our clamp-on flow meter installation guide. If your water carries solids or air, read transit-time vs Doppler ultrasonic flow meters first. For circulating cooling water, boiler make-up water and condensate in thermal and CHP plants, see ultrasonic flow meters in power plants.

Water flow meter suppliers: what to ask before you buy

Before you compare water flow meter suppliers, send each one the same pipe and process data, and ask the same questions. A clamp-on ultrasonic meter is configured to the measuring point, so a quotation is only comparable when it is based on the real outer diameter, wall thickness, pipe material, liner, water temperature, velocity range, output and power supply.

Buyer's checklist: the data a supplier needs for a water flow meter quotation

ItemWhy it mattersHow to get itSEGMENsensor reference
Pipe outer diameter and wall thicknessThe meter calculates flow from the inner area, so an error in OD or wall becomes a fixed error in every readingCircumference tape for OD; ultrasonic thickness gauge or pipe schedule for the wallDN15–DN5000 depending on the model (U11 15–5000 mm)
Pipe material and linerSets the sound velocity in the wall and the signal strength; cement or rubber linings must be enteredDrawings or utility records; check at an exposed flangeSteel, stainless steel, copper, cast iron, PVC, PE and most plastics
Water temperatureSelects the transducer typeProcess data sheet, maximum and minimum−40 to +80 °C standard sensors; +130 °C (H1A) and +180 °C (H2A) on the U10 series
Flow and velocity rangeThe accuracy statement applies inside the velocity rangeDesign flow ÷ inner area; convert units with the flow unit converter±0.01 to ±12 m/s (U11, U20); ±0.03 to ±5 m/s (U10 series)
Accuracy classDecides between control, water balance and indication dutiesYour metering or contract requirement±0.5% (U11); ±1% (U10, U10S PRO, U20); ±2% (U12); <3% FS (U13)
Output and protocolMust match the PLC, SCADA or BMS inputControl system I/O listChoose two of 4-20 mA, RS485 Modbus, pulse (OCT) and relay, depending on the model
Power supplyPanel DC supply or mains AC at the meter locationSite electrical drawing10–36 V DC; 90–245 V AC optional on the U10 series and standard choice on the U11
Installation spaceStraight run and transmitter location limit where the meter can goSite photo with straight lengths markedAt least 10D upstream and 5D downstream; transmitter IP65, sensors IP68
Quantity and scheduleDrives the quotation and the production planProject or annual volumeSamples 1–5 pcs in 5–7 working days; production lead time and MOQ confirmed with the quotation

Questions to ask any water flow meter supplier

  • Under what conditions is the accuracy stated? Ask for the velocity range, straight run and calibration behind the figure, not only the percentage.
  • Which transducer type is quoted, and what is its temperature rating? Standard, high-temperature and small-pipe transducers are different parts.
  • How many outputs are included? On the SEGMENsensor U10, U10S PRO and U11 you choose two outputs; state all the signals your control system needs.
  • Are the datasheet, manual and wiring diagram available before the order? SEGMENsensor publishes them on the ultrasonic flow meter downloads page; the U11 has its own U11 clamp-on ultrasonic flow meter datasheet (PDF).
  • Which certificates and warranty apply? SEGMENsensor clamp-on meters carry CE and UKCA, with a 12-month warranty; quotations are FOB China.
  • Can samples be tested on the real pipe first? Qualification samples of 1–5 pcs ship in 5–7 working days.
SEGMENsensor U11 high-accuracy wall-mount clamp-on ultrasonic flow meter, ±0.5% accuracy, for water pipes from 15 to 5000 mm
SEGMENsensor U11 high-accuracy clamp-on flow meter: ±0.5% accuracy, 0.1% repeatability and 15–5000 mm pipe range for water mains and large lines.

Pipe material and lining: what changes on site

PipeTypical water useWhat to checkMounting note
Carbon steelPump stations, boiler feed, chilled waterRust and scale at the contact points; internal scale on old linesClean to bare metal; Z-mode if the V-mode signal is weak
Stainless steel, copperProcess water, building servicesWall thickness on thin-walled tubeW- or V-mode on small, clean pipes
Cast or ductile ironWater supply mainsCement lining and its thicknessEnter liner material and thickness; Z-mode on large diameters
PVC, PEDistribution, irrigation, treated waterActual OD and wall, which vary by pressure classMeasure OD on site rather than using the nominal size

Typical applications (evaluated per project)

Municipal water and district metering. Fixed U10 or U10S PRO meters on distribution mains, or the U11 on pipes above 1200 mm, send flow to SCADA over RS485 Modbus. The portable U20 checks a district inlet before a permanent meter is installed.

Building services and data centers. Chilled and condenser water loops use the U10 series or the U11 energy (BTU) version with PT1000 sensors, connected to the BMS over Modbus. Our data center cooling water flow monitoring guide lists the measuring points and model per point.

Irrigation and agricultural water. Pumped irrigation mains in PE or PVC suit a fixed U10 with 4-20 mA to the pump controller, or the U20 for seasonal checks. The pipe must run full at the measuring point, so avoid high points and gravity sections that can drain.

What Affects the Cost of an Ultrasonic Water Flow Meter

We do not publish list prices because the configuration drives the quotation. The main factors are the pipe size range and transducer type, the accuracy class, the output and communication options, the enclosure and transducer protection rating, any certification required by your project, and order quantity. Quotations are FOB China and exclude international freight and import duties or taxes; payment is 100% T/T in advance, and meters carry a 12-month warranty.

SEGMENsensor sensor factory in Shenzhen: production and calibration area for OEM flow meters and sensors
SEGMENsensor manufactures and calibrates sensors in Shenzhen, China for 200+ OEM customers in 30+ countries.

Get a clamp-on ultrasonic flow meter for your water project

Fixed or portable, DN15 to DN5000 depending on the model, with 4-20 mA, RS485 Modbus RTU or pulse output. OEM volume supply · samples 1–5 pcs in 5–7 days · production lead time confirmed with the quotation · quotation within 24 hours. Download the clamp-on flow meter datasheet (PDF).

Frequently Asked Questions

Yes. A clamp-on meter measures drinking water from outside the pipe, so no part of the meter touches the water and the line does not need to be cut or drained. SEGMENsensor clamp-on meters cover water pipes from DN15 to DN5000 depending on the model, with ±0.5% accuracy on the U11 and ±1% on the U10 series and U20.

The SEGMENsensor U11 is specified at ±0.5% with 0.1% repeatability, U10, U10S PRO and U20 at ±1% (0.2% repeatability on the U10 series), U12 at ±2% (±1% after calibration) and U13 at <3% FS (<1.5% FS after calibration). These values assume a full pipe, correct pipe data entry and at least 10D straight run upstream and 5D downstream.

Yes. Transit-time clamp-on meters work on steel, stainless steel, copper, cast iron, PVC, PE and most plastics. Thick internal linings and heavily corroded or scaled pipe walls weaken the ultrasonic signal, so state the pipe material and any liner in your inquiry.

A transit-time meter works on clean, single-phase water such as treated effluent, cooling water and boiler make-up water. Raw sewage or slurry with a high solids or air content scatters the ultrasonic signal; for those liquids, describe the medium in your inquiry so the suitable measuring principle can be confirmed.

On U10, U10S PRO and U11 meters you choose two of 4-20 mA for a PLC analog input, RS485 or RS232 Modbus for SCADA or BMS, a pulse (OCT) output for totalizing and a relay output for alarms, with HART as an option. For heat and chilled-water energy metering, every model is available as an energy (BTU) version with PT1000 temperature sensors.

Qualification samples of 1–5 pcs ship in 5–7 days and production lead time and MOQ are confirmed with the quotation. Quotations are FOB China, sent within 24 hours on working days, and depend on pipe size range, output, transducer type, certification and quantity.

At least 10 pipe diameters (10D) of straight pipe upstream and 5D downstream of a single elbow, tee or fully open valve, measured to the transducers. On a DN100 water line that is about 1.0 m upstream and 0.5 m downstream (calculated). Pumps, control valves and out-of-plane elbows need a longer upstream run.

Look for another location first: after the next single elbow, or on a vertical section with upward flow, where the pipe stays full. If no location meets 10D / 5D, use Z-mode, mount the transducers as far downstream of the disturbance as possible and state the pipe layout in your inquiry so the quotation can note the expected accuracy.

The U13 covers DN15–DN40, the U12 DN15–DN65, and the U10S PRO and U11 start at 15 mm. On clean, thin-walled pipes from DN15 to DN50, W-mode mounting lengthens the ultrasonic path and improves resolution; the U10 and U20 start at 25 mm.

Ask under what velocity range and installation conditions the accuracy is stated, which transducer type and temperature rating are quoted, how many outputs are included, and whether the datasheet, manual and wiring diagram are available before the order. Send every supplier the same pipe OD, wall thickness, material, liner, water temperature, flow range, output and power supply so the quotations are comparable.

For permanent metering on PE or PVC irrigation mains, a fixed U10 with a 4-20 mA output to the pump controller is the usual choice; the battery-powered U20 portable meter suits seasonal checks across several pumps. Measure the actual pipe OD and wall on site, and choose a section that always runs full.

Yes. The U11 has its own datasheet at /downloads/segmensensor-u11-clamp-on-ultrasonic-flow-meter-datasheet.pdf, and the other models are covered by the clamp-on ultrasonic flow meter datasheet. Manuals, wiring diagrams and certificates are on the ultrasonic flow meter downloads page.

Last updated: 16 November 2026 — added the water flow meter supplier checklist, pipe material table, typical applications and three FAQs. 31 October 2026 · SEGMENsensor Engineering Team. First published 2 October 2026.