Quick Answer

A coolant level sensor for a liquid-cooled BESS container or a data center CDU monitors the reservoir that feeds the pump. SEGMENsensor supplies a non-contact ultrasonic sensor (25–1200 mm, 4-20 mA + two relay alarms, IP67), float level switches for point alarms, and hydrostatic transmitters for large tanks with samples in 5–7 days.

Liquid cooling has moved from a niche into the default design for two fast-growing systems: battery energy storage containers, where cells are cooled by a water-glycol loop, and AI or high-density server racks, where a coolant distribution unit (CDU) circulates dielectric coolant or treated water to cold plates. Both loops share a weak point. The reservoir or expansion tank is the only place where a slow leak, evaporation or an air pocket shows up before the pump cavitates or a cold plate runs dry. This guide explains what the level sensor in that reservoir has to do, which sensing technology suits each loop, and how the published specifications of SEGMENsensor liquid level sensors map onto the requirement. For the complete CDU sensor set including flow and pressure, see the CDU liquid-cooling sensor guide.

Why Coolant Level Is the First Alarm in a Liquid-Cooling Loop

A closed cooling loop is designed to hold a fixed volume. Any change in reservoir level is therefore information: a falling level means coolant is leaving the loop through a fitting, a quick-disconnect or a permeable hose; a rising level in a system with a heat exchanger can mean facility water is crossing into the secondary loop. Temperature and flow sensors report the consequence of a leak only after the cooling capacity has already dropped. The level sensor reports the cause, usually hours or days earlier.

Three functions are expected from the reservoir level sensor in both BESS and CDU designs:

  • Low-level pump protection. A relay contact or a switch output wired into the pump interlock so the pump cannot run dry.
  • Continuous level trend. A 4-20 mA or RS-485 signal to the battery management system (BMS), PLC or rack management controller, so that slow loss can be trended and a top-up scheduled before an alarm.
  • High-level or overflow alarm. A second contact for thermal expansion overfill or for facility-water ingress across the heat exchanger.

Three Sensing Technologies for a Coolant Reservoir

The reservoir in a CDU is usually a small polymer tank with a sight window; the expansion tank in a BESS container is larger and often stainless steel or HDPE. The coolant itself may be deionised water, a propylene-glycol or ethylene-glycol mixture, or a dielectric fluid. Each combination favours a different sensing method.

TechnologyHow it measuresBest fitOutput
Ultrasonic, non-contactTop-mounted transducer measures the echo time to the coolant surface; no wetted partsCDU reservoirs with dielectric coolant or DI water; polymer tanks (HDPE, polycarbonate, acrylic window)4-20 mA continuous + 2× relay alarm
Magnetic float switchA float carrying a magnet operates a reed contact or microswitch at one or more fixed pointsBESS expansion tanks and any loop that only needs low/high alarms; water-glycol with PP, PVDF or 316L wetted partsRelay / SSR contact; multi-float versions with 4-20 mA
Submersible hydrostatic transmitterPressure of the coolant column above the sensor, converted linearly to levelLarge buffer or storage tanks at container or plant level, 0.5 m and deeper4-20 mA / 0-10 V / RS-485 Modbus
Magnetostrictive level transmitterFloat position read along a rigid probe, 25–8000 mmTall storage tanks where high-resolution continuous level and optional temperature are required4-20 mA / RS485 / SSI

For most CDU reservoirs the ultrasonic sensor is the natural choice because nothing metallic touches the coolant, which matters for dielectric fluids and for deionised water that must stay low in conductivity. For BESS containers the float switch is often sufficient, since the control system needs a hard low-level interlock more than a continuous reading; a multi-float rod adds a 4-20 mA signal where the BMS wants a trend. Tank-farm and plant-level coolant storage is covered by the magnetostrictive level transmitter or a submersible transmitter.

Coolant Level Monitoring in Liquid-Cooled BESS Containers

Battery energy storage containers with liquid-cooled battery racks that use a water-glycol cooling loop monitored by coolant level sensors
Liquid-cooled BESS containers: the cooling loop expansion tank is where a slow coolant loss is detected first.

A liquid-cooled battery container typically runs a water-glycol loop through cold plates under each battery module, with a chiller and an expansion tank mounted in the thermal management compartment. The loop operates at modest pressure and at coolant temperatures from below freezing in winter storage to the chiller return temperature. The level sensor sits on the expansion tank and has to tolerate the glycol mixture, outdoor ambient swings and container vibration during transport.

The SEGMENsensor float level switch family is specified for this duty: reed-chain or microswitch operation, PP, PVDF or SUS 316L wetted materials for glycol compatibility, an operating temperature range of −40 °C to +120 °C (high-temperature version to 150 °C), IP67 or IP68 protection, and side-entry, top-entry or flanged mounting. A two-point float switch gives the BMS a low-level interlock and a high-level alarm from a single tank penetration. Where the site operator wants to trend coolant loss across a fleet of containers, the multi-float version with a 4-20 mA output feeds the same BMS analogue input as the pressure and temperature transmitters.

Because BESS containers are shipped as complete units, the sensor should be ordered with the final cable length, connector and gland so that no rework is needed at the integration line. SEGMENsensor builds these variants to order with the same sample policy (samples of 1–5 pcs).

Coolant Level Monitoring in Data Center CDUs

Data center server hall with liquid-cooled racks served by coolant distribution units that require reservoir level monitoring
Liquid-cooled server racks: the CDU reservoir level sensor protects the pump and gives the rack management controller an early leak indication.

Data centers are among the most energy-intensive building types, and the U.S. Department of Energy describes them as consuming many times the energy per floor area of a typical office building in its overview of Data Centers and Servers ↗. Direct liquid cooling is one of the main responses to that load. The CDU that serves a row or a rack contains a pump, a heat exchanger and a small reservoir, and the reservoir level is the primary indication that the secondary loop is intact.

The SEGMENsensor CDU coolant level sensor is a top-mounted ultrasonic sensor with no metal parts in contact with the fluid. It is compatible with dielectric coolant, deionised water and PAG or PGW mixtures, and with the HDPE, polycarbonate and acrylic-window tanks used in CDU chassis. The sensing range of 25–1200 mm covers reservoirs from a 1U in-rack CDU to a row-level unit, with ±1 mm accuracy over ranges up to 300 mm. Output is 4-20 mA continuous plus two relay alarms for low and high level, so the rack management controller receives a trend and the pump interlock receives a hard contact from the same device. The operating temperature of −10 °C to +60 °C matches the CDU environment, and the DC 12–24 V supply is taken from the CDU control board.

Specification Summary

All figures below are taken from the SEGMENsensor liquid level sensor product page. The ultrasonic column applies to the CDU coolant level sensor; the float column applies to the standard magnetic float level switch used on BESS expansion tanks.

ParameterUltrasonic coolant level sensor (CDU)Magnetic float level switch (BESS)
Measurement principleUltrasonic, non-contactMagnetic float, reed chain or microswitch
Sensing range25 mm – 1200 mmTank depth up to 10 m (multi-float rod)
Accuracy±1 mm (≤300 mm range)Switch point (N/A)
Output4-20 mA + 2× relay alarmRelay / SSR; 4-20 mA on multi-float versions
MediaDielectric coolant, DI water, PAG, PGWWater-glycol, water, oils (per wetted material)
Wetted / housing materialNo wetted parts; housing suits HDPE, polycarbonate, acrylic tanksPP / PVDF / SUS 316L
MountingTop-mount, G¾ thread or custom bracketSide entry / top entry / flanged
Operating temperature−10 °C to +60 °C−40 °C to +120 °C (HT version to 150 °C)
Supply voltageDC 12–24 VSwitch contact; DC 12–36 V or AC 230 V on powered versions
Protection ratingIP67IP67 / IP68
Hazardous areaSafe areaATEX/IECEx option
CertificationsCE, RoHS; ISO 9001:2015 factoryCE, RoHS; ISO 9001:2015 factory
Samples / lead timeQualification samples (1–5 pcs) in 5–7 days · production lead time confirmed with the quotation · reply within 24 hours

Protection ratings quoted above follow the IP code defined in IEC 60529 — Degrees of protection provided by enclosures (IP Code) ↗. IP67 covers the condensation and wash-down exposure inside a CDU chassis; IP68 is specified for float switches that may be fully submerged in a BESS expansion tank.

Download the one-page datasheet (PDF)

The liquid level sensor datasheet lists the float switch, submersible, ultrasonic and CDU coolant level sensor variants with ranges, outputs, materials, temperature limits, IP ratings, dimensions and the ordering code. No registration required.

Need a coolant level sensor specified for your BESS or CDU loop?

Send tank height, coolant type, mounting and quantity to our engineers. OEM volume supply · samples in 5–7 days · reply within 24 hours.

Integration: Outputs, Alarms and Wiring

The continuous level signal is a 2-wire 4-20 mA loop of the type defined in IEC 60381-1 — Analogue signals for process control systems, Part 1: Direct current signals ↗, so it connects to any BMS, PLC or rack controller analogue input without a converter. The live zero at 4 mA lets the controller distinguish an empty reservoir from a broken sensor cable. Where the controller network is serial, the RS-485 Modbus RTU option carries level and alarm status on one bus with the flow and pressure transmitters. Wiring practice for 2-wire and 3-wire loops is covered in how to wire a 4-20 mA transmitter; the same rules apply to level transmitters.

Relay alarms should be wired fail-safe: use the normally-closed contact for the low-level pump interlock so that a lost supply to the sensor also stops the pump. Set the low-level point above the pump suction with margin for tilt during BESS container transport and for the sloshing that occurs when a rack-level CDU is wheeled into position.

What Alarm Points Should a BESS or CDU Coolant Loop Have?

Short answer

A liquid-cooling loop needs at least three level points on the reservoir (high, low and low-low) and one pressure transmitter on the pump supply line, with a second one on the return line when filter or cold-plate fouling must be tracked. The low-low point trips the pump interlock; the others warn the BMS or rack controller.

  • Level tells you the cause. A falling reservoir level points to a leak; a rising level points to thermal overfill or facility-water ingress.
  • Pressure tells you the flow path. Low supply pressure points to the pump or trapped air; a growing supply–return difference points to a blocked filter or fouled cold plate.
  • The interlock must fail safe. Wire the low-low contact normally-closed so a broken cable stops the pump instead of hiding the alarm.
Diagram of a BESS or CDU coolant loop showing reservoir level alarm points H, L and LL, an ultrasonic level sensor, a float switch, and pressure transmitters on the pump supply and return lines
Where the level and pressure alarm points sit in a liquid-cooling loop: H, L and LL on the reservoir, PT on the pump supply and on the return from the cold plates.

The table below lists each alarm, which sensor provides it and how the set point is chosen. Set points are defined by the loop designer from the tank drawing, the pump suction height and the normal operating pressure band; SEGMENsensor builds the float points and relay thresholds to the positions you specify.

AlarmSensor and signalHow to choose the set pointTypical action
Level high (H)Upper float point or ultrasonic relay 2Below the tank overflow or vent, leaving room for coolant expansion at the maximum operating temperatureWarning; check for facility-water ingress across the heat exchanger or overfilling after service
Level low (L)Ultrasonic 4-20 mA trend or middle float pointThe level at which a planned top-up is needed, well above the pump suctionWarning to BMS or rack controller; schedule top-up and a leak inspection
Level low-low (LL)Lower float point, normally-closed contactAbove the pump suction, with margin for container tilt during transport and for sloshing when a rack CDU is movedTrip the pump interlock or derate the system
Supply pressure lowPressure transmitter, 4-20 mA, on the pump dischargeBelow the normal operating pressure band recorded at commissioningAlarm; check pump, air in the loop or a leak downstream
Supply pressure highSame transmitterAbove the normal band and below the relief-valve settingAlarm; check for a closed valve or blocked filter
Supply–return difference risingSecond pressure transmitter on the return lineAbove the clean-filter baseline recorded at commissioningPlan filter change or cold-plate inspection

For the pressure points, a SEGMENsensor pressure transmitter covers ranges from 0–0.1 bar to 0–400 bar with ±0.25% FS accuracy as standard (±0.1% FS high-accuracy version) and a 4-20 mA, 0-10 V or RS-485 output, so the same analogue inputs that read the level sensor can read loop pressure. For a deep storage or buffer tank at plant level, a submersible level transmitter gives the continuous level trend instead of a top-mounted sensor.

Download the pressure transmitter datasheet (PDF)

Ranges, outputs, process connections, materials and the ordering code for the pressure transmitters used on coolant supply and return lines. No registration required.

How Do You Inspect Coolant Level and Pressure Alarms? A 7-Step Checklist

Inspect them at commissioning and then at every scheduled maintenance visit set by the system operator, using the same seven steps so that readings can be compared over time.

SEGMENsensor stainless steel pressure transmitters of the type used to monitor coolant supply and return pressure in liquid-cooling loops
A stainless steel SEGMENsensor pressure transmitter of the type fitted on the pump supply and return lines of a coolant loop.
  1. Record the baseline. At commissioning, write down the reservoir level signal (mA or %) and the supply and return pressures at normal flow. Every later reading is compared with this baseline.
  2. Check the live zero. Read each 4-20 mA signal at the controller. A value below 4 mA means an open loop or a sensor fault, not an empty tank or zero pressure.
  3. Function-test the low-low interlock. Lower the float or disconnect the contact and confirm the pump stops. Restore it and confirm the pump restarts only after the alarm is acknowledged.
  4. Test the H and L warnings. Move the float or adjust the ultrasonic relay threshold and confirm both messages reach the BMS or rack controller.
  5. Compare the level trend. A steady fall between visits means a leak somewhere in the loop; a rise means ingress or overfilling. Investigate before the next top-up.
  6. Check the pressure zero. With the loop depressurised and vented, a gauge pressure transmitter should read close to zero. A drift beyond the stated accuracy calls for recalibration or replacement.
  7. Inspect sensor faces and glands. Clean condensation or deposits from the ultrasonic face and the float stem, check cable glands for the specified IP rating, then bleed air after any top-up and record a new baseline.

Selection Checklist

What to include in your first enquiry
  • Reservoir: internal height (or depth), material (HDPE, polycarbonate, stainless steel), and the available mounting position (top, side or flange).
  • Coolant: deionised water, glycol type and concentration, or dielectric fluid; operating and storage temperature.
  • Function: continuous level (4-20 mA / RS-485), point alarms (relay), or both; number of switch points.
  • Interface: supply voltage available on the control board, cable length, connector or gland type.
  • Environment: IP rating required, vibration during transport, ATEX zone if the container is classified.
  • Quantity: sample count now and expected annual volume, plus destination (quotations are FOB China).

OEM Supply for BESS and CDU Integrators

Segmen Industrial Development Co., Ltd. was founded in Shenzhen in 2019; its engineering team brings more than 20 years of sensor experience and supplies 200+ OEM customers in 30+ countries. Coolant level sensors are built to order on an ISO 9001:2015 production line, so the sample that passes qualification on your CDU or container prototype is the same configuration that ships in the series order. Custom brackets, cable lengths and connectors are available for rack and container integration, and private-label documentation can be supplied for the integrator's own manual.

SEGMENsensor OEM sensor manufacturing facility in Shenzhen — assembly, calibration and testing of liquid level sensors and industrial sensors
SEGMENsensor OEM manufacturing and testing facility, Shenzhen. Sample and production coolant level sensors are built and tested on the same line.

Frequently Asked Questions

A non-contact ultrasonic level sensor mounted on top of the reservoir. Nothing touches the dielectric coolant or deionised water, the 25–1200 mm range covers typical CDU tanks, and the 4-20 mA output plus two relay alarms connect directly to the rack management controller.

Yes. Float level switches with PP, PVDF or 316L stainless steel wetted parts and the ultrasonic non-contact sensor are both compatible with water-glycol mixtures used in liquid-cooled battery containers. State the glycol type and concentration on the enquiry so the wetted material is confirmed.

Continuous 4-20 mA (2-wire) or 0-10 V for level, RS-485 Modbus RTU on request, and relay contacts for low-level and high-level alarms. Float switches provide a direct relay or solid-state switch output for pump interlocks.

The CDU ultrasonic coolant level sensor is rated −10 °C to +60 °C on the coolant side, matching the CDU environment. Float level switches cover −40 °C to +120 °C as standard, with a high-temperature version up to 150 °C for hot-side loops.

OEM volume supply, qualification samples of 1–5 pieces shipped in 5–7 days, production lead time and MOQ are confirmed with the quotation, and every enquiry answered within 24 hours. Custom brackets, cable lengths and connectors are available for rack and container integration. The factory is ISO 9001:2015 certified and sensors carry CE and RoHS.

Above the pump suction, with enough margin for container tilt during transport and for sloshing when a rack CDU is moved. Wire it as a normally-closed contact into the pump interlock so a lost supply or broken cable also stops the pump.

Level shows whether coolant is leaving or entering the loop; pressure shows whether it is flowing. A pressure transmitter on the pump supply line detects pump faults, trapped air and blocked filters that a reservoir level sensor cannot see.

At commissioning and at every scheduled maintenance visit set by the system operator. Each test checks the 4-20 mA live zero, trips the low-low interlock, confirms the high and low warnings, and compares level and pressure with the commissioning baseline.

Related reading: Clamp-on flow meters for ESS water-glycol loops and battery test benches · Liquid level sensors — product page · CDU liquid-cooling sensor guide (level, flow, pressure) · Float level switch selection guide · How to choose a liquid level sensor · Submersible level transmitters · Pressure transmitters
Last updated: 12 October 2026. Specifications reflect the SEGMENsensor product page at the date of publication; contact us for the current datasheet revision.