Quick Answer

Use PV = LRV + (I − 4) ÷ 16 × (URV − LRV) to turn current into a process value, and I = 4 + 16 × (PV − LRV) ÷ (URV − LRV) to go the other way. 12 mA is mid-scale; each 1.6 mA is 10 % of span.

4–20 mA scaling calculator

Current% of spanProcess value

Fault check follows the common NAMUR NE 43 convention: below 3.6 mA or above 21 mA = sensor or wiring fault; 3.8–20.5 mA = valid measurement with saturation.

The 4–20 mA scaling formula

Current → value: PV = LRV + (I − 4 mA) ÷ 16 mA × (URV − LRV)

Value → current: I = 4 mA + 16 mA × (PV − LRV) ÷ (URV − LRV)

Percent of span: % = (I − 4) ÷ 16 × 100

LRV and URV are the lower and upper range values set in the transmitter. The 16 mA span is fixed, so the same formula works for pressure, level, flow, temperature or position — only the range changes.

Worked examples

Transmitter rangeReadingCalculationResult
Pressure 0–10 bar8 mA0 + (8 − 4) ÷ 16 × 102.5 bar
Pressure 0–400 bar15.2 mA(15.2 − 4) ÷ 16 × 400280 bar
Level 0–5 m17.6 mA(17.6 − 4) ÷ 16 × 54.25 m
Position 25–1000 mm12 mA25 + 0.5 × 975512.5 mm
Compound −1 to +5 bar4 mA → 20 mALRV = −1, URV = 5−1 bar → 5 bar

Why the signal starts at 4 mA, not 0 mA

The 4 mA "live zero" powers two-wire transmitters through the loop itself and lets the receiver distinguish a genuine 0 % reading (4 mA) from a broken wire or dead transmitter (0 mA). Current is also immune to the voltage drop of long cable runs, which is why 4–20 mA remains the standard analogue signal for process instruments (IEC 60381-1).

Reading fault currents

Loop currentUsual meaningFirst check
0 mAOpen loop: broken wire, no supply, blown fuseMeasure supply voltage at the transmitter terminals
< 3.6 mATransmitter signals an internal fault (NE 43 low alarm)Transmitter diagnostics, sensor element
3.8–20.5 mAValid measurement (including slight over/under-range)—
> 21 mAHigh alarm or short circuit across the loopWiring for shorts, transmitter alarm setting

Wiring two-wire and three-wire transmitters is covered step by step in our 4–20 mA wiring guide; for choosing a transmitter see the selection guide and the 4–20 mA pressure transmitter page.

Standards & Further Reading

Frequently Asked Questions

12 mA is always 50 % of the configured range, because 12 mA is halfway between 4 mA and 20 mA. On a 0–10 bar transmitter, 12 mA means 5 bar.

Use PV = LRV + (I − 4) ÷ 16 × (URV − LRV). For a 0–16 bar transmitter reading 10 mA: (10 − 4) ÷ 16 × 16 = 6 bar.

0 mA almost always means an open loop (broken wire or no supply). Readings below about 3.6 mA are commonly used by transmitters to signal an internal fault (NAMUR NE 43 convention).

0.16 mA, because the span is 16 mA. 10 % of span is 1.6 mA.

Yes. Set the lower range value below zero, e.g. −1 to +5 bar for a compound range; 4 mA then means −1 bar.