Why is 4–20 mA everywhere? This one-minute video explains the series current loop, the scaling formula I = 4 + 16 × value ÷ span (6 bar on a 0–10 bar range is 13.6 mA), why the live zero starts at 4 mA, and how a 250 Ω resistor turns 4–20 mA into 1–5 V in the PLC.

Chapters

  1. 0:00Introduction
  2. 0:04One series loop
  3. 0:144 mA to 20 mA = range
  4. 0:26The scaling formula
  5. 0:35Why start at 4 mA
  6. 0:45The 250 Ω resistor
  7. 0:54Summary

Key points

  • Transmitter, power supply and PLC input form one series loop; the same current flows through every part.
  • 4 mA is the bottom of the range and 20 mA is full scale (here 0–10 bar).
  • I = 4 + 16 × value ÷ span: 6 bar on a 0–10 bar range gives 13.6 mA (calculated value).
  • The live zero shows a broken wire as 0 mA, can power a 2-wire transmitter, and cable resistance does not change the signal.
  • A 250 Ω resistor in the PLC turns 4–20 mA into 1–5 V.

Transcript

4–20 mA: why is it everywhere?

A 4–20 mA transmitter, its power supply and the PLC input form one series loop. The same current flows through every part of it.

The current represents the measured value. 4 mA is the bottom of the range, 20 mA is full scale. Here, 0–10 bar.

The formula: I = 4 + 16 × value ÷ span. At 6 bar, that is 13.6 mA.

Why start at 4? A live zero shows a broken wire as 0 mA, it can power a 2-wire transmitter, and cable resistance does not change the signal.

In the PLC, a 250 Ω resistor turns 4–20 mA into 1–5 V.

SEGMENsensor pressure transmitters with 4–20 mA output. Try our free calculator at segmensensor.com.

Standards and references

Related pages

Send the range, process connection and output — we confirm the transmitter and quote samples.Get a quote →

Request a Quote — SEGMENsensor pressure transmitters

Send the range, process connection and output — we confirm the transmitter and quote samples. Engineers reply within 24 hours.

Samples 1–5 pcs in 5–7 days · lead time and MOQ confirmed with the quotation · info@segmensensor.com

info@segmensensor.com